The 8-15KW Three-phase Home Inverter is an innovative solution for both residential and small commercial solar systems. With a power range of 8kW up to 50kW, the inverter is designed with world-advanced inverter control technology that has a high maximum efficiency of up to 98.8%. It has an ultra-low startup voltage as low as 160V and a maximum input current of 22A to better support most high-efficiency solar modules for higher yields. Sleek, family-style design with aluminum-magnesium alloy stretch technology provides strength with aesthetic appeal. Ultraquiet operation as low as 29dB allows it to be placed anywhere.
Parameter | 8kw | 10kw | 12kw | 15kw |
---|---|---|---|---|
Maximum Input Voltage (V) | 1100 | 1100 | 1100 | 1100 |
MPPT Voltage Range (V) | 140-1000 | 140-1000 | 140-1000 | 140-1000 |
Start Voltage (V) | 160 | 160 | 160 | 160 |
Rated Input Voltage (V) | 600 | 600 | 600 | 600 |
Maximum Input Current per MPPT (A) | 22 | 22 | 22 | 22 |
Maximum Short-Circuit Current per MPPT (A) | 27.5 | 27.5 | 27.5 | 27.5 |
Number of MPPTs | 2 | 2 | 2 | 2 |
Modules per MPPT String | 1 | 1 | 1 | 1 |
Rated Output Power (W) | 8000 | 10000 | 12000 | 15000 |
Maximum Active Power Output (W) | 8800 | 11000 | 13200 | 16500 |
Maximum Apparent Power Output (VA) | 8800 | 11000 | 13200 | 16500 |
Nominal Output Voltage (V) | 380/3L/N/PE or 3L/PE | 380/3L/N/PE or 3L/PE | 380/3L/N/PE or 3L/PE | 380/3L/N/PE or 3L/PE |
Output Voltage Frequency (Hz) | 50 | 50 | 50 | 50 |
Maximum Output Current (A) | 13.4 | 16.7 | 20.0 | 25.0 |
Total Harmonic Distortion | <3% | <3% | <3% | <3% |
Maximum Efficiency | 98.5% | 96.5% | 98.6% | 98.6% |
Chinese Efficiency | 98.1% | 98.1% | 98.7% | 98.2% |
DC Current Monitoring | Optional | Optional | Optional | Optional |
Insulation Resistance Detection | Integrated | Integrated | Integrated | Integrated |
Leakage Current Detection | Integrated | Integrated | Integrated | Integrated |
Input Reverse Protection | Integrated | Integrated | Integrated | Integrated |
Weak Grid Protection | Integrated | Integrated | Integrated | Integrated |
AC Overcurrent Protection | Integrated | Integrated | Integrated | Integrated |
AC Short-Circuit Protection | Integrated | Integrated | Integrated | Integrated |
AC Overvoltage Protection | Integrated | Integrated | Integrated | Integrated |
DC Switch | Integrated | Integrated | Integrated | Integrated |
DC Arc Fault Protection | Three levels (Two levels optional) | Three levels (Two levels optional) | Three levels (Two levels optional) | Three levels (Two levels optional) |
AC Surge Protection | Three levels (Two levels optional) | Three levels (Two levels optional) | Three levels (Two levels optional) | Three levels (Two levels optional) |
DC Control Strength Protection | Optional | Optional | Optional | Optional |
RSD | Optional | Optional | Optional | Optional |
PID Repair | Optional | Optional | Optional | Optional |
Night Supply | Optional | Optional | Optional | Optional |
IV Curve Scan | Optional | Optional | Optional | Optional |
Working Temperature Range (°C) | -30 to 60 | -30 to 60 | -30 to 60 | -30 to 60 |
Relative Humidity | 0-100% | 0-100% | 0-100% | 0-100% |
Maximum Working Altitude (m) | 4000 | 4000 | 4000 | 4000 |
Cooling Method | Natural cooling | Natural cooling | Natural cooling | Natural cooling |
Human-Machine Interaction | LED, LCD (Optional) | LED, LCD (Optional) | LED, LCD (Optional) | LED, LCD (Optional) |
Communication Method | RS485, 4G | RS485, 4G | RS485, 4G | RS485, 4G |
Weight (Kg) | 14.7 | 14.7 | 15.5 | 15.5 |
Dimensions (W x H x D mm) | 491 x 392 x 204 | 491 x 392 x 204 | 491 x 392 x 204 | 491 x 392 x 204 |
Topology Structure | Isolated | Isolated | Non-isolated | Non-isolated |
Night Self-Consumption (W) | <1 | <1 | <1 | <1 |
Protection Level | IP66 | IP66 | IP66 | IP66 |
Certification Standards | Grid standard | Grid standard | Grid standard | Grid standard |
Safety Standard | NB/T32004 | NB/T32004 | NB/T32004 | NB/T32004 |
EMC Standard | NB/T 32004 | NB/T 32004 | NB/T 32004 | NB/T 32004 |