The 40-50KW three-phase high voltage energy storage inverter is the advanced solution for medium and small-scale commercial and residential energy applications. This series comes in power capacities of 40kW and 50kW and is able to support multi-machine parallel operations to configure scalable systems. Fitted with an STS switch for switchover without interruption, this inverter can work as a UPS system and support generator integration. Compatible with high-power solar modules up to 210mm and 182mm components, the system allows for a maximum input current of 21A and 1.1x of continuous overload on the grid side. Safety features are enhanced with DC arc protection and dual AC/DC surge protection that guarantee safe operation of your energy system in various environments.
Parameter | 40KW | 50KW |
---|---|---|
Rated Input Voltage (V) | 620 | 620 |
Start Voltage (V) | 160 | 160 |
MPPT Voltage Range (V) | 165~850 | 165~850 |
Maximum Input Current per MPPT (A) | 42/32/42 | 42/32/42/32 |
Maximum Short-Circuit Current per MPPT (A) | 55/42/55 | 55/42/55/42 |
Number of MPPTs | 3 | 4 |
Modules per MPPT String | 2 | 2 |
Rated Grid-Tied Output Apparent Power (VA) | 40,000 | 50,000 |
Maximum Grid-Tied Output Apparent Power (VA) | 44,000 | 55,000 |
Maximum Input Apparent Power (VA) | 44,000 | 55,000 |
Rated Output Voltage (V) | 380, 3L/N/PE | 380, 3L/N/PE |
Output Voltage Frequency (Hz) | 50 | 50 |
Maximum Grid-Tied Output Current (A) | 66.7 | 83.3 |
Maximum Input Current (A) | 66.7 | 83.3 |
Power Factor | - | - |
Total Current Waveform Distortion Rate | <3% | <3% |
Off-Grid Rated Apparent Power (VA) | 40,000 | 50,000 |
Maximum Output Apparent Power (VA) | 44,000 (48,000 at 60sec, 60,000 at 10sec) | 55,000 (60,000 at 60sec, 70,000 at 10sec) |
Maximum Output Current (A) | 66.7 | 83.3 |
Rated Output Voltage (V) | 380 | 380 |
Rated Output Voltage Frequency (Hz) | 50 | 50 |
Total Voltage Waveform Distortion Rate (@Linear Load) | <3% | <3% |
Maximum Efficiency | 98.10% | 98.10% |
Battery Side⇄AC Side Maximum Efficiency | 97.70% | 97.70% |
Insulation Resistance Detection | Integrated | Integrated |
Residual Current Monitoring | Integrated | Integrated |
Anti-Islanding Protection | Integrated | Integrated |
Input Reverse Protection | Integrated | Integrated |
AC Overcurrent Protection | Integrated | Integrated |
AC Short-Circuit Protection | Integrated | Integrated |
AC Overvoltage Protection | Integrated | Integrated |
Working Temperature Range (℃) | -35~+60 | -35~+60 |
Relative Humidity | 0~95% | 0~95% |
Maximum Working Altitude (m) | 4,000 | 4,000 |
Cooling Method | Smart Air Cooling | Smart Air Cooling |
Human-Machine Interaction | LED, APP | LED, WLAN+APP |
BMS Communication Method | RS485, CAN | RS485, CAN |
Meter Communication Method | RS485 | RS485 |
Weight (Kg) | 62.0 | 65.0 |
Dimensions (W x H x D mm) | 520x660x260 | 520x660x260 |
Topology Structure | Non-isolated | Non-isolated |
Night Self-Consumption (W) | <15 | <15 |
Protection Level | IP66 | IP66 |
Installation Method | Wall Mount | Wall Mount |